CAT24-EN

Overall dimensions and technical information are provided solely for informative purposes and may be modified without notice 1 Air distribution Solenoid valves manifold 1 | 17 Series PX - Inputs and outputs modules ►Analogue outputs module kit M8 Coding: K5130.CS C CHANNELS 2 = 2 channels 4 = 4 channels S SIGNAL T.00 = VOLTAGE (0-10 V) T.01 = VOLTAGE (0-5 V) C.00 = CURRENT (4-20 mA) C.01 = CURRENT (0-20 mA) M8 analogue outputs module converts output data, received from field bus via network node, into analogue signal. Outputs module power supply is provided by + 24 V DC power input on the serial system (type A, 4 pins M12 power connector, pin 4) or by K5030.M12 additional power supply module, in case it were installed upstream of the outputs module. Technical characteristics Protection (pin 1) Overcurrent (auto-resettable fuse) Protection (pin 4) Overcurrent (auto-resettable fuse) Digital conversion resolution 12 bit Maximum cable length < 30 m Output data allocation 16 bit per channel Diagnostic LED Output signal overcurrent Accuracy 0,3% F.S. Overall maximum current 2 channels (pin 1) 300 mA Overall maximum current 4 channels (pin 1) 750 mA (375 mA for each pair of channels) INPUTS + 24 V DC current consumption of the module only 15 mA OUTPUTS + 24 V DC current consumption of the module only (2 channels) 35 mA OUTPUTS + 24 V DC current consumption of the module only (4 channels) 70 mA Scheme / Overall dimensions and I/O layout 4 3 1 PIN 1 3 4 0 V OUTPUT 90 28 42 90 28 42 M8 3P female connector DESCRIPTION + 24 V DC (OUTPUTS)

RkJQdWJsaXNoZXIy NzYzOTY1