CATGEN-EN

Overall dimensions and technical information are provided solely for informative purposes and may be modified without notice 8 Input Module 1 AIR DISTRIBUTION Solenoid valves manifold 1 | 444 Series 2200 "OPTYMA-S" - Serial systems 52 104 156 208 General: Scheme / Overall dimensions and I/O layout : 5222.08S Module 1 Module 1 Module 2 Module 1 Module 2 Module 3 Module 1 Module 2 Module 3 Module 4 PIN DESCRIPTION 1 +24 VDC 4 INPUT 3 GND 1 4 3 Modules have 8 connectors M8 3P female. The Inputs are PNP equivalent 24 VDC ±10%. To each connector it is possible to plug both 2 wires Inputs (switches, magnetic switches pressure switches, etc) or 3 wires Inputs (proximity, photocells, electronic sensors, etc). The maximum current available for all 8 Inputs is 300 mA. Each module includes a 300 mA self-mending fuse. If a short circuit or a overcharge (overall current >300mA) occur the safety device acts cutting the 24 VDC power supply to all M8 connectors on the module and switching off the green LED PWR. Any other Input module connected to the node will remain powered and will function correctly. Once the cause of the fault disappears the green LED PWR lights up indicating the ON state and the node will re-start to operate. The maximum number of Input modules supported is 4. Ordering code M8 3P FEMALE CONNECTOR M8 3P FEMALE CONNECTOR