CATGEN-EN

Overall dimensions and technical information are provided solely for informative purposes and may be modified without notice 8 Input Module 1 Air distribution Solenoid valves manifold 1 | 481 Series 2500 "OPTYMA-F" - Serial systems 76.6 153.2 229.8 306.4 Module 1 Module 2 Module 3 Module 4 GREEN LED POWER GREEN LED INPUTS M8 3P FEMALE CONNECTOR M8 3P FEMALE CONNECTOR Ordering code 1 4 3 PIN DESCRIPTION 1 +24 VDC 4 INPUT 3 GND Modules have 8 connectors M8 3P female. The Inputs are PNP equivalent 24 VDC ±10%. To each connector it is possible to plug both 2 wires Inputs (switches, magnetic switches pressure switches, etc.) or 3 wires Inputs (proximity, photocells, electronic sensors, etc). The maximum current available for all 8 Inputs is 200 mA. Each module includes a 200 mA self-mending fuse. If a short circuit or a overcharge (overall current >200mA) occur the safety device acts cutting the 24 VDC power supply to all M8 connectors on the module and switching off the green LED PWR. Any other Input module connected to the node will remain powered and will function correctly. Once the cause of the fault disappears the green LED PWR lights up indicating the ON state and the node will re-start to operate. The maximum number of Input modules supported is 4. General: Scheme / Overall dimensions and I/O layout : 5225.08F Module 1 Module 1 Module 2 Module 1 Module 2 Module 3