CATGEN-EN

Overall dimensions and technical information are provided solely for informative purposes and may be modified without notice 16 Input Module 1 Air distribution Solenoid valves manifold 1 | 482 Series 2500 "OPTYMA-F" - Serial systems Ordering code General : Modules are fitted with SUB-D 25 pin female connector. The Inputs are PNP equivalent 24VDC ±10%. To the connector it is possible to connect both 2 wires Inputs (switches, magnetic switches pressure switches etc.) or 3 wires (proximity, photocells, electronic end of stroke sensors etc). The maximum current available for all 16 Inputs is 750 mA. Each module includes a 750 mA self-mending fuse. Should a short circuit or a overcharge (overall current >750mA) occur the safety device intervenes cutting the 24VDC power supply to all pins and switching off the green LED PWR. Any other Input module connected to the node will remain powered and will function correctly. Once the cause of the fault is removed the green LED lights up indicating the ON state and the node will re-start to operate. This16 Inputs module is counted as two 8 Inputs modules The Maximum number of 16 Inputs modules supported is 2 for CANopen® , DeviceNet and EtherCAT® .The Maximum number of 16 Inputs modules supported is 4 for PROFIBUS DP, PROFINET IO RT, EtherNet/IP and Powerlink. Scheme / Overall dimensions and I/O layout : GREEN LED POWER GREEN LED INPUTS SUB-D25 P FEMALE CONNECTOR 5225.25F Module 1 Module 1 Module 2 INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 INPUT 7 INPUT 8 +24 VDC +24 VDC GND GND N.C. 1 13 14 25 INPUT 9 INPUT 10 INPUT 11 INPUT 12 INPUT 13 INPUT 14 INPUT 15 INPUT 16 +24 VDC GND GND +24 VDC 76.6 153.2

RkJQdWJsaXNoZXIy NzYzOTY1