NW96-EN

M8 analogue outputs modules Solenoid valves manifold Series 3000 - Inputs and outputs modules 46 Overalldimensionsand technical informationareprovidedsolely for informativepurposesandmaybemodifiedwithoutnotice AIR DISTRIBUTION General - M8 analogue outputs modules kit M8 analogue outputs module converts output data, received from field bus via network node, into analogue signal. Power supply of the M8 analogue outputs module is provided by 24VDC power input on the serial system (type A, 4 pin M12 power connector, pin 4) or by 5030.M12 additional power supply module, in case it were installed upstream of the outputs module. Ordering code Scheme / Overall dimensions and I/O layout M8 3P female connector 4 3 1 PIN DESCRIPTION 1 +24 VDC (OUTPUTS) 3 GND 4 OUTPUT K5130._ _.0_ CODE SIGNAL ANALOGUE OUTPUTS MAX. CURRENT PER MODULE (pin1) OCCUPIED OUTPUTS K5130.2T.00 VOLTAGE 0-10V 2 1 A 32 (4 bytes) K5130.2T.01 VOLTAGE 0-5V 2 1 A 32 (4 bytes) K5130.4T.00 VOLTAGE 0-10V 4 2 A (1A for each pair of channels) 64 (8 bytes) K5130.4T.01 VOLTAGE 0-5V 4 2 A (1A for each pair of channels) 64 (8 bytes) K5130.2C.00 CURRENT 4-20mA 2 1 A 32 (4 bytes) K5130.2C.01 CURRENT 0-20mA 2 1 A 32 (4 bytes) K5130.4C.00 CURRENT 4-20mA 4 2 A (1A for each pair of channels) 64 (8 bytes) K5130.4C.01 CURRENT 0-20mA 4 2 A (1A for each pair of channels) 64 (8 bytes) Technical data Protection (pin 1) Overcurrent (auto-resettable fuse) Protection (pin 4) Short circuit (electronic), trigger at 20mA Digital conversion resolution 12 bit Maximum cable length < 30m Output data allocation 16 bit per channel Diagnostic LED Output signal overcurrent Precision 0,3% F.S. Available models 42 90 28 42 90 28